A3-40
IM 34M06C11-01E
Note
Take the following corrective actions for problems encountered during the installation.
- In case of noise leakage from the opening for the cable, wrap the cables using shield
covers, shield tubes, conduit pipes, etc. to prevent noise leakage.
Item
Manufacturer
Product
Shield cover
Nitto Industries, Inc.
SDF-03-04-35ES
Shield tube
Nippon Zipper Tubing, Inc.
OTFX series
MTFX series
SHX series
SHNX series
Conduit pipe
Nitto Industries, Inc.
EMP series
- In case of noise leakage from the ventilation hole, install an electromagnetic shield
filter.
Item
Manufacturer
Product
Electromagnetic shield for the
ventilation hole
Nitto Industries, Inc.
RSLP series
- In the case of noise leakage from the gap between the panel enclosure and the door,
use electromagnetic shield gasket to fill the gap.
Item
Manufacturer
Product
Electromagnetic shield
gasket
Kitagawa Industries, Inc.
UC series
Nippon Zipper Tubing, Inc.
65TS series
- Using a grounding strap to connect the metal plate and the door to the panel
enclosure itself may achieve better grounding.
Item
Manufacturer
Product
Grounding strap
Kitagawa Industries, Inc.
FGM series
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...