A2-52
IM 34M06C11-01E
(16) F3YA08-2N Triac Output Module
Item
Specifications
Item
Specifications
Output type
Triac contact
Service
life
Mechanical
─
Number of points
8
Electrical
─
Common line type
8 points/common
Surge protector
*1
CR absorber, varistor
Isolation method
Photocoupler isolation
Fuse
*2
4A time-lag fuse (Built into
the COM terminal and
cannot be replaced.)
Withstanding voltage
1500V AC for one minute
between the group of
connectors for external
connection and the
internal circuit
Dissipating current
130mA (5V DC)
Rated load voltage
range (maximum
load voltage)
DC
─
Output display
*3
LED (Lit when output is on)
AC 100-240V (264V)
Maximum load current
1A/point (0 to 40
C)
0.7A/point (40 to 55
C)
3A/common line
Output status when the
program stops
HOLD/RESET
*4
When a sequence CPU
module is used:
Default: RESET
Can be set globally on a
module-by-module basis.
Minimum load
voltage/current
24V AC,10 mA/point
When a BASIC CPU module
is used:
No setting function
The status is always HOLD
Response
time
OFF
→
ON
1ms max.
ON
→
OFF
1/ 1ms max.
External power supply
Not required
ON voltage
1.5V AC max.
External connection
10-points terminal block with
M3.5 screws
Off-time leak current
3mA max.
Weight
150g
*1:
If an inductive load, such as a relay, is to be connected, a surge protector is also required on the load side. Connect
a surge protector across the load nearby so that the module output terminal voltage will not exceed the specified
operating load voltage range. For details, see Subsection A3.6.5, “Connecting Output Devices.”
*2:
Fuses in the output module are for the purpose of preventing abnormal heat generation or burnout of external wiring
due to continuous flow of excess short-circuit current resulting from a short-circuited load.
They are not intended for protecting output elements in the module against possible damage.
The fuses may fail to blow in failure modes other than short-circuited loads.
*3:
The contact operation of the output block of the circuit and the LED display operate independently and thus may be
inconsistent in the event of an error.
*4:
For information on the module’s behavior during a CPU failure, see subsection A4.3.3, “Indicating Problem Severity
and Status of Output Module.”
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...