C1-3
IM 34M06C11-01E
C1.2
Restrictions on Module Installation
C1.2.1
Restrictions on Module Location
Install the F3SP08-0P sequence CPU in slot 1 for the F3SC22-
□□
, and install the
F3SP08-SP sequence CPU module in slot 1 for the F3SC23-
□□
. Install the other
specified component modules in slot 2 (or slots 2 and 3). You may install FA-M3 I/O
modules in the remaining slots. You may not install a CPU module in the remaining
slots.
For restrictions on the installation of I/O modules, including subunits, refer to Section
A1.2, “Restrictions on Module Installation,” as they are equivalent to the restrictions
specified for the F3SP21-0N module discussed in that section.
C1.2.2
Restrictions due to Current Consumption
Make sure when designing your system that the total sum of current consumed by any
modules installed in the remaining slots does not exceed the following calculated value.
See section A2.9, "Module Current Consumption Tables".
Total Amount of Current Available from the Remaining Slots
F3SC22-1F/F3SC23-1F
1500mA
F3SC22-2F/F3SC23-2F/F3SC23-2P/F3SC23-6P 1400mA
F3SC22-1A/F3SC23-1A
1415mA
Current-supply Capacity, Current Consumption of each Module
F3SP08-0P/F3SP08-SP Current-supply Capacity of Power Supply Unit
2000mA
F3SP08-0P/F3SP08-SP Current Consumption of CPU Unit
350mA
F3BU04-0N
Current Consumption
50mA
F3WD32-3F
Current Consumption
100mA
F3WD64-3F
Current Consumption
200mA
F3WD64-3P
Current Consumption
170mA
F3WD64-4P
Current Consumption
170mA
F3XD16-3F
Current Consumption
65mA
F3YD14-5A
Current Consumption
120mA
Therefore, the total amount of current available from the remaining slots is the current-
supply capacity of the power supply unit (2000mA) less the current consumption of all
pre-installed modules.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...