A2-83
IM 34M06C11-01E
(30) F3WD64-3P/F3WD64-4P Input/Output Modules (with short-circuit
protector)
Input Block
Item
F3WD64-3P
F3WD64-4P
Input type
DC voltage
Number of points
32 (terminal Nos. 01 - 32)
Common line type
8 points/common
Isolation method
Photocoupler isolation
Withstanding voltage
1500V AC for one minute between the group of terminals for external
connection and the internal circuit
Rated input voltage
(
operating voltage range
)
24V DC
(
20.4 to 26.4V DC
)
12V DC
(
10.2 to 13.2V DC
)
Rated input current
4.1mA/point (24V DC)
4.1mA/point (12V DC)
Input impedance
5.9kΩ
2.9kΩ
Operating
voltage/current
ON
16.0V DC min.
3.2mA min.
8.0V DC min.
2.6mA min.
OFF
5.8V DC max.
0.9mA max.
3.4V DC max. 1.0mA max.
Response time
OFF
→
ON
Input sampling time can be specified for 4 steps: Always (0μs), 62.5μs, 250μs,
and 1ms.
*1
ON
→
OFF
Input sampling time can be specified for 4 steps: Always (0μs), 62.5μs, 250μs,
and 1ms.
*1
Interrupt
None
Withstanding voltage
1500V AC for one minute between the group of terminals for external
connection and the internal circuit
Input display
*2
Lit when input is on (Input or output status indication can be selected using a
switch.)
Dissipating current
170mA (5V DC) (for input and output)
External connection
One 40-pin connector
Weight
120g (for input and output)
Maximum ratio of inputs turned on
simultaneously
60%
100%
*1:
These values are applicable when using the module with CPU module using F3SP22, F3SP28, F3SP38, F3SP53,
F3SP58, F3SP59, F3SP66, F3SP67, F3SP71 or F3SP76 module. If other CPU modules are used, the values for
OFF
ON and for ON
OFF are 1.0 ms and 2.5 ms max. respectively. The actual response time is obtained by
adding about 100
s for OFF
ON and about 300
s for ON
OFF to the specified value.
If input interrupt is to be used, set the input sampling time to 62.5μs or more.
*2:
The contact operation of the output block of the circuit and the LED display operate independently and thus may be
inconsistent in the event of an error.
Output Block
Item
F3WD64-3P
F3WD64-4P
Output type
Transistor contact (sink type)
Number of points
32 (terminal Nos. 33 - 64)
Common line type
8 points/common
Isolation method
Photocoupler isolation
Withstanding voltage
1500V AC for one minute between the group of terminals for external
connection and the internal circuit
Rated load voltage
(Operating load voltage range)
24V DC
(20.4 to 26.4V DC)
12V DC
(10.2 to 13.2V DC)
Maximum load current
0.1A/point, 0.4A/common line
Response time
OFF
→
ON
1ms max.
ON
→
OFF
1ms max.
ON voltage
0.5V DC max.
Off-time leak current
0.1mA max.
Protection circuitry
Short-circuit
Controlled short-circuit current
Overheat
Output shutdown
Surge protector
*3
Active clamp
Fuse
None
Output status when the program
stops HOLD/RESET
*4
When a sequence CPU module is used:
Default: RESET
Can be set globally on a module-by-module basis
*5
When a BASIC CPU module is used:
No setting function
The status is always HOLD
External power supply
24V DC, 55mA
12V DC, 55mA
Output status display
*6
Lit when output is on (Input or output status indication can be selected using
a switch.)
Dissipating current
170mA (5V DC) (for input and output)
External connection
One 40-pin connector
Weight
120g (for input and output)
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...