B2-1
IM 34M06C11-01E
B2.
Specifications and Configuration
B2.1
Specifications
Common Specifications
Item Specifications
Supply voltage range
100 to 240V
AC, single phase 50/60Hz
Range of supply voltage change
85 to 264V AC, 50/60Hz ± 3Hz
Power consumption
35VA
Insulation resistance
5M
Ω
min. when tested between a group of external AC terminals and the FG terminal using a
500V DC insulation resistance tester
5M
Ω
min. when tested between a group of FAIL-signal contact output and internal circuit using a
500V DC insulation resistance tester.
Withstanding voltage
1500V AC for one minute between a group of external AC terminals and the FG terminal
1000V AC for one minute between a group of FAIL-signal contact output and internal circuit.
FAIL-signal contact output
Located on the front terminal block of power supply module;
contact ratings: 24V DC, 0.3A
(Equipped with both normally-open and normally-closed terminals)
Leakage current
3.5mA max.
Allowable momentary power failure time
20ms
Noise immunity
Tested using a noise simulator with a noise voltage of 1500Vp-p, pulse width of 1µs, rise time of 1
ns, and repetition frequency of 25 to 60Hz.
Vibration resistance
Tested in compliance with JIS C60068-2-6 under the following conditions:
- Frequency ranges:
10 to 57Hz with an amplitude of 0.075mm
57 to 150Hz with an acceleration of 9.8m/s
2
(1G)
- Direction and sweep cycles: 10 times each in the X, Y, and Z directions
Shock resistance
Tested in compliance with JIS C60068-2-27 under the following conditions:
- Direction and sweep cycles: 3 times each in the X, Y, and Z directions with an acceleration of
147m/s
2
(98m/s
2
with DIN-rail mounting)
Surrounding air temperature range
Operating
:
0 to 55°C
Storage
:
-20°C to 75°C
Surrounding humidity range
Operating
:
10 to 90% RH (non-condensing)
Storage
:
10 to 90% RH (non-condensing)
Surrounding atmosphere
Must be free of corrosive gases, flammable gases or heavy dust.
Grounding Protective
earth
(Comply with the regulation of each country.)
Cooling method
Natural-air cooled
Mounting
Direct mounting with 4 M4-size set screws
*1
or 35-mm wide DIN-rail mounting
Structure
Designed for mounting inside a panel enclosure
Altitude of installation
Max. of 2000m above sea level
Compliance with safety
standards
*2
UL
UL508 approved, File No.E188707
(Overvoltage Category
*3
:
II, Pollution Degree
*4
:
2)
Finish color
Light cobalt blue, equivalent to Munsell 6.2PB 4.6/8.8;
lampblack, equivalent to Munsell 0.8Y 2.5/0.4
External dimensions
147 (W)× 100 (H)× 88.5 (D)(mm)
For more information, see the dimensional figures in Section A2.11, “External Dimensions,” for the
case where an F3BU04-0N module is used
*1:
For details on the number of mounting screws, see subsection A3.2.2, “Mounting Dimensions”.
*2:
For details on conforming modules, see Appendix A2, “Standard compliant products”.
*3:
The term Overvoltage Category involves prescriptions on resistance to surge voltage reduction due to lightning and has
four categories. Overvoltage Category II applies to systems with a rated voltage of 220/230/240V and applies to electrical
appliances, portable devices, etc.
*4:
The term Pollution Degree represents the degree of pollution with foreign matter, solid, liquid or gaseous, that may produce a
reduction of dielectric strength or surface resistivity in the operating environment of the equipment. Pollution degree 2 refers to
an environment where normally only non-conductive pollution occurs but occasionally temporary conductivity caused by
condensation is to be expected.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...