A3-19
IM 34M06C11-01E
Immediate Detection Mode
(when F3PU16-0N, F3PU16-0S, F3PU26-0N, F3PU26-0S, F3PU36-0N or F3PU36-0S is used)
Momentary Power Failure Detection
- System operation continues without interruption even if the power fails momentarily
for no longer than 2ms (undetected momentary power failure).
- If a power failure longer than 2ms and less than 10ms occurs, the controller may or
may not recognize a momentary power failure condition because an uncertainty is
involved. When the controller detects a momentary power failure, it holds or resets
its outputs (in accordance with the output set at stop) , it suspends program
execution, and then it turns on the FAIL contact. (Refer to Section A2.3 of this
manual for details on how the FAIL contact works). It also records the date and time
at which the momentary power failure occurred into the error log file in the CPU.
The controller restarts in the reset restart mode after a momentary power failure is
detected.
- The controller always detects any momentary power loss conditions that are longer
than 10ms.
Power Failure Detection
The entire functionality of the controller is disabled when the CPU operating voltage
(+5V) falls below 95% of the rated voltage.
Automatic Recovery
The controller resumes normal operation automatically when the power recovers from a
momentary power failure condition and the CPU operating voltage (+5V) rises above
95% of the rated voltage. The controller restarts in the reset restart mode following the
detection of a power failure condition.
Power on/off sequences
ON
Allowable momentary
power failure time
Momentary power
failure detected
Power failure
detected
Power restored
Power supply
Power Loss
Detected
CPU operating
voltage (+5V)
Reset
Program
FAIL 1 contact
OFF
ON
OFF
ON
Approx. 2 s
Approx. 2 s
OFF
Power
shutdown
Power-on
2 ms or less
Longer than 2 ms
Momentary power
failure detected
Power failure detected
Reset restart
Reset restart
Longer than 2 ms
and less than 10 ms
Approx. 3 s
Approx.3 s
FA030308.VSD
Figure A3.16 Detection of Abnormal Supply Voltage Levels in Immediate Detection Mode
(for F3PU16, F3PU26 and F3PU36)
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...