A2-87
IM 34M06C11-01E
(31) F3WD64-3F/F3WD64-4F Input/Output Modules
Input Block
Item
Specifications
F3WD64-3F
F3WD64-4F
Input type
DC voltage
Number of points
32 (terminal Nos. 01 - 32)
Common line type
8 points/common
Isolation method
Photocoupler isolation
Withstanding voltage
1500V AC for one minute between the group of terminals for
external connection and the internal circuit
Rated input voltage
24V DC
12V DC
Operating voltage range
20.4 to 26.4V DC
10.2 to 13.2V DC
Rated input current
4.1mA/point
(24V DC)
4.1mA/point
(12V DC)
Input impedance
5.9k
Ω
2.9k
Ω
Operating
voltage/current
ON
16.0V DC min.
3.2mA min.
8.0V DC min.
2.6mA min.
OFF
5.8V DC max.
0.9mA max.
3.4V DC max.
1.0mA max.
Response time
OFF
→
ON
Input sampling time can be specified for 4 steps: Always (0μs),
62.5μs, 250μs, and 1ms.
*1
ON
→
OFF
Input sampling time can be specified for 4 steps: Always (0μs),
62.5μs, 250μs, and 1ms.
*1
Interrupt
None
Dissipating current
200mA (5V DC) (for input and output)
Input display
LED (Lit when inputs are turned on)
If the selector switch is set to IN, the input state is displayed.
External connection
One 40-pin connector
Weight
160g (for input and output)
Maximum ratio of inputs turned on
simultaneously
60%
100%
*1:
These values are applicable when using the module with CPU module using F3SP22, F3SP28, F3SP38, F3SP53,
F3SP58, F3SP59, F3SP66, F3SP67, F3SP71 or F3SP76 module. If other CPU modules are used, the values are
the same as those for F3WD64- N modules. The actual response time is obtained by adding about 100
s for
OFF
ON and about 300
s for ON
OFF to the specified value.
If the input sampling time is set to a very small value, the modules become susceptible to noise. In such a case,
implement countermeasures against noise as described in Section A3.4 "Noise Control Considerations" and Section
A3.9 "CE Marking Compliance".
If input interrupt is to be used, set the input sampling time to 62.5μs or more.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...