A2-19
IM 34M06C11-01E
(4) F3PU36-0N/F3PU36-0S Power Supply Module
Specifications
Item
Specifications
F3PU36-0N/F3PU36-0S
*1
Supply voltage
24V DC
Range of supply voltage
change
15.6 to 31.2V DC
Power consumption
46.2W
Inrush current
20A max. (31.2V DC, Ta=25°C)
Fuse
Time-lag fuse
(Built into the positive terminal and cannot be replaced.)
Rated output voltage
5V DC
Rated output current
6.0A
Insulation resistance
5M
min. when tested between a group of external DC terminals and the
FG terminal using a 500V DC insulation resistance tester
5MΩ min. when tested between a group of FAIL-signal contact output and
internal circuit using a 500V DC insulation resistance tester.
Withstanding voltage
1500V AC for one minute between a group of external
DC terminals and the FG terminal
1000V AC for one minute between a group of FAIL-signal contact output and
internal circuit.
Allowable momentary
power failure time
20ms
External dimensions
58 (W)
×
100 (H)
×
126.1 (D) mm
*2
Weight
410g
Compatible base module
Dedicated to F3BU05, F3BU09, F3BU13 and F3BU16
*1:
The only difference between modules F3PU30-0N and F3PU30-0S lies in the screw diameter of their screw terminal
blocks.
*2:
Excluding protrusions (see the dimensional figures for more information)
Components and Their Functions
The figure below shows the power supply modules with their covers removed.
Across FAIL 1 and COM
Across FAIL 2 and COM
Open
Short
Short
Open
Normal operating time
System Failure and
Power Failure Times
FAIL signal contact output
Contact ratings: 24 V DC, 0.3 A
FG (
Frame Grou nd
)
LG (
Line filter Ground
)
Power supply
Functional earth
Functional earth
24V DC
Lit when the power supply
module is normal.
RDY indicator (green)
FA020307.VSD
F3PU36-0N/F3PU36-0S
RDY
FAIL1
COM
FAIL2
FAIL
OUTPUT
FG
LG
INPUT
24VDC
P OWER
PU36-0N
+
Figure A2.5 F3PU36-0N/F3PU36-0S Power Supply Module
WARNING
To avoid electrical shock, turn off the power before wiring.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...