B1-3
IM 34M06C11-01E
B1.2
Restrictions on Module Installation
B1.2.1
Restrictions on Module Location
In the case of the F3SC21-1N, install the F3SP05-0P in slot 1 and the F3WD64-3N in
slot 2. The remaining slots 3 and 4 are reserved for a variety of I/O modules available
for use with the FA-M3 series. No CPU module can be installed in slots 3 and 4. For
restrictions on the installation of I/O modules, including subunits, refer to Section A1.2,
“Restrictions on Module Installation,” as they are equivalent to the restrictions specified
for the F3SP21-0N module discussed in that section.
B1.2.2
Restrictions due to Current Consumption
Make sure when designing your system that the total sum of current consumed by
modules installed in slots 3 and 4 does not exceed the following calculated value.
See section A2.9, "Module Current Consumption Tables".
Current-supply capacity of the F3SP05-0P module = 2000mA
Current consumption by the CPU of the F3SP05-0P module = 350mA
Current consumption of the F3BU04-0N module = 50mA
Current consumption of the F3WD64-3N module = 200mA
Consequently, the total amount of current available from slots 3 and 4 is
2000 – 350 – 50 – 200 = 1400mA
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...