A2-16
IM 34M06C11-01E
Terminal dimensions
F3PU30-0N
F3PU30-0S
FA020306.VSD
7.1mm
8.2mm
M3.5
7.1mm
8.2mm
M4
Adaptable crimp-on terminals
Vendor
Model
Compatible Conductor
Crimping Torque
F3PU30-0N
F3PU30-0S
Japan Solderless
Terminal Mfg Co., Ltd.
V1.25-M3
AWG22 to 18
(0.33 to 0.82mm
2
)
(Copper wire)
0.8N
m
(7.1 lbf
in)
May not be
used
Nippon Tanshi Co., Ltd.
RAV1.25-3.5
Japan Solderless
Terminal Mfg Co., Ltd.
V1.25-M4
1.2N
m
(10.6 lbf
in)
Japan Solderless
Terminal Mfg Co., Ltd.
V2-M4
AWG16 to 14
(1.3 to 2.1mm
2
)
(Copper wire)
Note
When crimping terminals, be sure only to use the tool specified by each terminal
manufacturer.
Once the power supply module is installed in the base module, both the FG terminal of
the power supply module and the signal ground (GND terminal of the module’s 5V
output) of the FA-M3 automatically come into contact with the metal chassis of the base
module. The FG terminal and the signal ground are isolated from each other inside the
power supply module.
For details on the grounding lines of the FA-M3, see subsection A3.3.2, “Grounding
Lines.”
Note
- F3PU30-0S module is the same as F3PU30-0N module, but it uses M4 terminal
screws instead of M3.5 terminal screws. Other than terminal screw diameter, their
dimensions and internal circuitries are identical.
- F3PU30-0N is not CE Marking compliant.
F3PU30-0S is CE Marking compliant.
- For compliance to CE Marking of the final product incorporating these modules,
F3PU30-0S must be used.
Note
Power supply circuit which is connected to FAIL signal contact output terminal must be
SELV and limited-energy circuit separated by reinforced insulation or double insulation
from hazardous voltage.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...