A3-23
IM 34M06C11-01E
A3.5.3
Power Supply Wiring
AC Power Supply Module
Model
Supply Voltage
Allowable Range of Supply Voltage Change
F3PU10-0N
F3PU10-0S
100-240V AC
85 to 264V AC
F3PU20-0N
F3PU20-0S
F3PU30-0N
F3PU30-0S
FA030501.VSD
INPUT
100-240VAC
~
PU 10-0N
RDY
POWER
F3PU10-0N
FAIL1
COM
FAIL2
LG
N
L
FAIL
OUTPUT
FG
PU 10-0N
RDY
POWER
FAIL1
COM
FAIL2
LG
N
L
FAIL
OUTPUT
FG
INPUT
100-240VAC
~
F3PU10-0N
Wire other AC power supply modules
in a similar manner.
Isolation
transformer
(1:1)
When an abnormal condition occurs in the
power supply module, the circuit across
the FAIL 1 and COM terminals is shorted
and the circuit across the FAIL 2 and
COM terminals is opened. The maximum
switching capacity of the module is 0.3 A
at 24 VDC.
Figure A3.20 Wiring the AC Power Supply Module
WARNING
To avoid electrical shock, turn off the power before wiring.