A2-12
IM 34M06C11-01E
A2.3
Power Supply Modules
(1) F3PU10-0N/F3PU10-0S/F3PU20-0N/F3PU20-0S Power Supply
Modules
Specifications
Item
Specifications
F3PU10-0N/ F3PU10-0S *
1
F3PU20-0N/ F3PU20-0S *
1
Supply voltage range
100 to 240V AC, single phase 50/60Hz
Range of supply voltage
change
85 to 264V AC 50/60Hz
±
3Hz
Power consumption
35VA
85VA
Inrush current
20A max. (120V AC, Ta=25°C)
45A max. (240V AC, Ta=25°C)
Fuse
Time-lag fuse
(Built into the L and N terminals
and cannot be replaced.)
Time-lag fuse
(Built into the L and N terminals and
cannot be replaced.)
Rated output voltage
5V DC
Rated output current
2.0A
4.3A
Insulation resistance
5M
min. when tested between a group of external AC terminals and the
FG terminal using a 500V DC insulation resistance tester
5MΩ min. when tested between a group of FAIL-signal contact output and
internal circuit using a 500V DC insulation resistance tester.
Withstanding voltage
1500V AC for one minute between a group of external AC terminals and
the FG terminal
1000V AC for one minute between a group of FAIL-signal contact output
and internal circuit.
Leakage current
3.5mA max
Allowable momentary power
failure time
20ms
External dimensions
28.9 (W)
×
100 (H)
×
83.2 (D) mm *
2
58 (W)
×
100 (H)
×
83.2 (D) mm *
2
Weight
190g
320g
Compatible base module
Dedicated to
F3BU04 and F3BU06
Dedicated to F3BU05, F3BU09,
F3BU13 and F3BU16
*1:
F3PU10-0N (respectively F3PU20-0N) and F3PU10-0S (respectively F3PU20-0S) have terminal blocks with different
screw sizes but are otherwise exactly the same.
*2:
Excluding protrusions (see the dimensional figures for more information)
Components and Their Functions
The figure below shows the power supply modules with their covers removed.
Figure A2.2 F3PU10-0N/F3PU10-0S and F3PU20-0N/F3PU20-0S Power Supply Modules
WARNING
To avoid electrical shock, turn off the power before wiring.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...