(4) Considerations on Cable Routing
Signal cables that are connected to the FA-M3 carry harmonic components. The signal
cable acts like an antenna and emits these harmonic components as noise to the
external space and at the same time receives the noise from the external space.
Therefore, it is necessary to use shielded signal cables.
The EMC conformance test of the FA-M3 is conducted using shielded cables and FG
clamps.
The considerations that should be observed during cable routing are summarized below.
Figure A3.38 illustrates this graphically.
- Of the signal cables connected to this equipment, those that lead out of the panel
enclosure should be shielded and the shield at both ends of the cable should be
grounded. 10BASE-T and 100BASE-TX cable sections that lead out of the panel
enclosure (say, to connect to a HUB) should be shielded.
Item
Manufacturer
Product
Shielded twisted cable
Fuji Cable Industries, Inc.
FKEV series
Shielded flat cable
Oki Cable, Inc.
SFX-S (**)-7/0.127
3030-SV series
Daichi Electrical Materials, Inc.
FDS series
Shielded 10BASE-T cable
Shielded 100BASE-TX cable
Allied Telsis, Inc.
Category V shielded cable
Sanwa Supply, Inc.
STP cable
Hitachi Cable, Inc.
HSTP5 4P
(without connector)
- Remove part of the covering on a shielded cable to expose the shield and ground it
to the metal plate of the panel enclosure by an FG clamp. When connected to the
metal plate in a pig-tail way using a drain wire, it cannot ensure low impedance
against harmonic noise and cannot provide sufficient grounding effect (noise shield
effect).
Item
Manufacturer
Product
FG clamp
Kitagawa Industries, Inc.
FGC series
- Power supply cables of power supply modules (F3PU30-0S and F3PU36-0S) and
YHLS Slave Units (TAH Series) should be fitted with ferrite cores to prevent
interference emission.
Item
Manufacturer
Product
Ferrite core
Kitagawa Industries, Inc.
RFC series
TDK, Inc.
ZCAT series
NEC Tokin, Inc.
ESD-SR series
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...