A4-11
IM 34M06C11-01E
(2) For the F3SP22, F3SP28, F3SP38, F3SP53, F3SP58 and F3SP59
Select [Online]–[Extended Functions] from the menu bar of the FA-M3 Programming
Tool WideField, WideField2 or WideField3.
T
For details, refer to the FA-M3 Programming Tool WideField (IM 34M06Q14-01E), the FA-M3 Programming Tool
WideField2 (IM 34M06Q15-01E) or the FA-M3 Programming Tool WideField3 (IM 34M06Q16-
E). F3SP22-0S supports
only the FA-M3 Programming Tool WideField3.
(3) For the F3SP21, F3SP25 and F3SP35
Use the Operation Setup menu of the Ladder Diagram Support Program M3.
T
For details, refer to the Ladder Diagram Support Program M3 (IM 34M06Q13-01E).
The operations can also be carried out using the FA-M3 Programming Tool WideField, WideField2 or WideField3 for
F3SP21-0N, F3SP25-2N, and F3SP35-5N modules.
(4) For the F3BP20-0N and F3BP30-0N BASIC CPU
- User area : Initialization using the NEW command.
- Common area
: Initialization using the INIT COM statement.
- Own CPU shared register area
: Initialization using the INICOMM3 library.
For details on the above-mentioned command, statement and library, refer to the BASIC CPU Modules and YM-
BASIC/FA Programming Language (IM 34M06Q22-01E).
Note
Methods of memory clearance when the FA-M3 Programming Tool WideField3 is
not available (for F3SP21/22/25/28/35/38/53/58/59 only)
If you mistakenly configure the baud rate of the CPU port to 19200 bps when running
the Ladder Diagram Support Program M3 on an earlier version of the PC98 series of
personal computers that does not support that baud rate, the communication link is
disabled and the program becomes no longer usable.
If this situation happens, follow the instructions given below.
Install a sequence CPU module in the 5th or higher slot and turn on the power. After
making sure the RDY lamp has gone out momentarily and then comes on again, turn off
the power. This clears the CPU memory completely, and restores the module to its
factory setting.
A4.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...