Table A4.2 Failure Severity Levels and Status of Output Module
(when the CPU module is F3SP22/28/38/53/58/59/66/67/71/76)
Severity
Level
LED
Indication
Effect Probable
Cause
P
*
5
Status of FAIL-signal
Contact Output
Status of Output Module
Between
FAIL1
and COM
Between
FAIL2
and COM
Output modules
other than
F3YD64-1A,
F3YD64-1M,
F3WD64-
□
N
F3YD64-1A,
F3YD64-1M,
F3WD64-
□
N,
Y
□□□□□
*3
Major
Green
RDY lamp
is off.
Core
hardware is
disabled.
• Hardware failure
• SPU error
*6
• Memory error
*6
Shorted
Open
Default: RESET
Can be set on a
16-point basis.
Setting ignored
The status is
always HOLD
Moderate Red ERR
lamp is lit.
The user
program
cannot be
started or
run any
further.
• Startup error
• Boot mode error
• SPU error
*6
• Memory error
*6
• Invalid instruction found
• Program error
• Power Failure While
Writing to a Flash ROM
/Flash memory error
• ROM pack error
• Battery error/Memory
check error
• Subroutine error
P
*1
• Interrupt error
P
*1
• Instruction error
P
*1
,
Macro
instruction error
*1
• I/O comparison error
P
*1
• I/O module error
P
*1
• Scan timeout
P
*1
• Sensor CB scan
timeout
P
*1
• Subunit communication
error
P
*2
P
Shorted
Open
Default: RESET
Can be set on a
16-point basis.
Default: RESET
Can be set on a
16-point basis.
Minor
Yellow
ALM lamp
is lit.
The program
can still run In
spite of a
minor failure
detected.
• Momentary power
failure
P
*4
• Inter-CPU
communication error
• Subunit transmitter
switching has occurred
• FA link error
Open
Shorted
Operation
continues.
Operation
continues.
*1:
The severity level of this error item can be set using the Error-time Action field under Operation Control of the
Configuration. Setting the field to "Stop" indicates a moderate failure whilst setting it to "Run" indicates a minor
failure. The default value is "Stop" (moderate failure).
*2:
The severity level of this error item can be set using the Error-time Action field under Operation Control of the
Configuration. Setting the field to "Stop" indicates a moderate failure whilst setting it to "Run" indicates a minor
failure. The default value is "Run" (minor failure).
*3:
Output relays (Y
□□□□□
) of the advanced modules.
*4:
When supply voltage abnormality is detected, output modules behave differently depending on whether the standard
mode or immediate detection mode is selected. Behaviors during momentary power failure in each mode are as
follows:
Supply Voltage
Abnormality
Detection mode
Status of FAIL-signal Contact Output
Status of Output Module
Between FAIL1 and
COM
Between FAIL2 and
COM
Output modules
other than
F3YD64-1A,
F3YD64-1M,
F3WD64-
□
N
F3YD64-1A,
F3YD64-1M,
F3WD64-
□
N,
Y
□□□□□
*3
Standard mode
Open
Shorted
Hold
Hold
Immediate
detection mode
Shorted
Open
Reset
Hold
*5:
It depends on model. Please refer to the user’s manual of each model.
*6:
Depending on the content, it may cause major failure and moderate failure.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...