A3-34
IM 34M06C11-01E
A3.7
External Cable Routing Requirements
It is especially desirable that the requirements given in this section be satisfied in the
routing of the controller’s signal cables, power supply cables and power-motive cables
of the devices.
Isolating Cables
When routing cables, segregate by at least 20cm cables that may become noise
sources such as power-motive cables and power supply cables from signal cables that
are susceptible to noise, as shown in figures A3.32 and A3.33.
If that is not possible, separate the cables by putting a separator between them as
shown in figure A3.34.
Signal cables
Power lines
20cm
min.
FA030701E.VSD
Signal
cables
20cm
min.
Power
lines
FA030702E.VSD
Figure A3.32 Segregation Using Cable Rack
Figure A3.33 Segregation in Parallel Routing
Signal
cables
Power
lines
Sep arator
Class C grounding
(10
max.)
FA030703E.VSD
Figure A3.34 Segregation Using Separator
Perpendicular Crossing of Cables
If the signal cables cross power-motive cables or power supply cables, lay them
perpendicular to each other. If no shielded cable is used, it is recommended that a steel
plate of at least 1.6mm thick be placed between the two sets of cables at their
intersection as shown by the dotted lines in Figure A3.35.
Signal cables
1.6mm or thicker
Power lines
FA030704E.VSD
Figure A3.35 Perpendicular Crossing of Cable
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...