A2-92
IM 34M06C11-01E
Output Block
Item
Specifications
F3WD64-3N
F3WD64-4N
Output type
Transistor contact (sink type)
Number of points
32 (terminal Nos. 33 - 64)
Common line type
8 points/common
Isolation method
Photocoupler isolation
Withstanding voltage
1500V AC for one minute between the group of terminals for
external connection and the internal circuit
Rated load voltage
(Operating load voltage range)
24V DC
(20.4 to 26.4V DC)
12V DC
(10.2 to 13.2V DC)
Maximum load current
0.1A/point, 0.4A/common line
Response time
OFF
→
ON
1ms max.
ON
→
OFF
1ms max.
ON voltage
0.5V DC max.
Off-time leak current
0.1mA max.
Service life
Mechanical
──
Electrical
──
Surge protector
*1
Zener diode
Fuse
None
Dissipating current
200mA (5V DC) (for input and output)
Output display
*2
LED (Lit when output is on)
Output state is displayed when the display selector is set to
“OUT”
Output status when the program
stops HOLD/RESET
*3
When a sequence CPU module is used:
Default: RESET
Can be set globally on a module-by-module basis.
*4
When a BASIC CPU module is used:
No setting function
The status is always HOLD
External power supply
24V DC, 60mA
12V DC, 60mA
External connection
One 40-pin connector
Weight
160g (for input and output)
*1:
If an inductive load, such as a relay, is to be connected, a surge protector is also required on the load side. Connect
a surge protector or a diode across the load nearby so that the module output terminal voltage will not exceed the
specified operating load voltage range. For details, see Subsection A3.6.5, “Connecting Output Devices.”
*2:
The contact operation of the output block of the circuit and the LED display operate independently and thus may be
inconsistent in the event of an error.
*3:
For information on the module’s behavior during a CPU failure, see subsection A4.3.3, “Indicating Problem Severity
and Status of Output Module.”
*4:
When F3SP22, F3SP28, F3SP38, F3SP53, F3SP58, F3SP59, F3SP66, F3SP67, F3SP71 or F3SP76 module is
used, this setting can be specified in 16-point units.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...