A3-22
IM 34M06C11-01E
A3.5
Wiring the Power Supply Module
A3.5.1
Re-checking Specifications
CAUTION
- Re-check the I/O specifications for the power supply module. Specifically, note that
connecting an AC power supply to a power supply module requiring DC input and
connecting a 200-240V AC power supply to a power supply module requiring 100-
120V AC input will lead to machine failure.
- To avoid electrical shock, turn off the power before wiring.
- Make sure that the ‘+’ , ‘–’ and FG terminals of a DC input power supply module and
the L, N and FG terminals of an AC input power supply module are connected
correctly.
A3.5.2
Wiring Materials
(1) Wire
Method of External
Connection
Compatible Conductor Size
Temperature
Rating
Material
Terminal block
AWG22 to 14 (0.33 to 2.1mm
2
)
75°C min
Copper
Use AWG14 (2.1mm
2
) for ground cabling.
(2) Terminal Screws and Crimp-on Terminals
The F3PU
-0S power supply modules use M4-screw terminal blocks, unlike
F3PU
-0N power supply modules, which use M3.5-screw terminal blocks. The
following crimp-on terminals are recommended for connecting to the power supply
modules:
Under 7mm
FA030601.VSD
Figure A3.19 Crimp-on Terminals
Vendor
Model
Compatible
Conductor
Compatible Modules and Crimping Torque
F3PU
□□
-0N
F3PU
□□
-0S
Japan Solderless
Terminal Mfg Co., Ltd.
V1.25-M3
AWG22 to 18
(0.33 to 0.82mm
2
)
(Copper wire)
0.8N
m
(7.1 lbf
in)
Cannot be used
Nippon Tanshi Co., Ltd.
RAV1.25-3.5
Japan Solderless
Terminal Mfg Co., Ltd.
V1.25-M4
1.2N
m
(10.6 lbf
in)
Japan Solderless
Terminal Mfg Co., Ltd.
V2-M4
AWG16 to 14
(1.3 to 2.1mm
2
)
(Copper wire)
Note
When crimping terminals, be sure only to use the tool specified by each terminal
manufacturer.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...