A2-2
IM 34M06C11-01E
Power Supply Specifications
Item
Specifications
F3PU10-0N
F3PU10-0S
F3PU20-0N
F3PU20-0S
F3PU30-0N
F3PU30-0S
F3PU16-0N
F3PU16-0S
F3PU26-0N
F3PU26-0S
F3PU36-0N
F3PU36-0S
Supply voltage range
100 to 240V AC, single phase 50/60Hz
24V DC
Range of supply voltage change
85 to 264V AC 50/60Hz
±
3Hz
15.6 to 31.2V DC
Power consumption
35VA 85VA
100VA
15.4W
33.1W 46.2W
Insulation resistance
5M
Ω
min. when tested between a group of external
AC terminals and the FG terminal using a 500V DC
insulation resistance tester
5M
Ω
min. when tested across a group of external DC
terminals and the FG terminal using a 500V DC insulation
resistance tester
5M
Ω
min. when tested between a group of FAIL-signal contact output and internal circuit using a 500V DC insulation
resistance tester.
Withstanding voltage
1500V AC for one minute between a group of
external AC terminals and the FG terminal
1500V AC for one minute between a group of external DC
terminals and the FG terminal
1000V AC for one minute between a group of FAIL-signal contact output and internal circuit.
FAIL-signal contact output
Located on the front terminal block of power supply module; contact ratings: 24V DC, 0.3A (Equipped with both
normally-open and normally-closed terminals)
Leakage current
3.5mA max.
Allowable momentary power failure time 20ms
* For detailed power supply module specifications, see A2.3, "Power Supply Modules."
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...