A2-59
IM 34M06C11-01E
(19) F3YD08-7A Transistor Output Module
Item
Specifications
F3YD08-7A
Output type
Transistor contact
(sink type)
Number of points
8
Common line type
8 points/common
Isolation method
Photocoupler isolation
Withstanding voltage
1500V AC for one minute between the group of terminals
for external connection and the internal circuit
Rated load voltage
(Operating load voltage
range)
DC
12-24V DC
(10.2 to 26.4V DC)
AC
───
Maximum load current
2A/point, 8A/common line
Response time
OFF
→
ON
1ms max.
ON
→
OFF
1ms max.
ON voltage
0.5V DC max.
Off-time leak current
0.1mA max.
Service life
Mechanical
───
Electrical
───
Surge protector
*1
Active clamp circuit
Fuse
*2
None
Dissipating current
80mA (5V DC)
Output display
*3
LED (Lit when output is on)
Output status when the program stops
HOLD/RESET
*4
When a sequence CPU module is used:
Default: RESET
Can be set globally on a module-by-module basis.
When a BASIC CPU module is used:
No setting function
The status is always HOLD
External power supply
12-24V DC, 10 mA
External connection
10-point terminal block with M3.5 screws
Weight
130g
*1:
If an inductive load, such as a relay, is to be connected, a surge protector is also required on the load side. Connect
a surge protector or a diode across the load nearby so that the module output terminal voltage will not exceed the
specified operating load voltage range. For details, see Subsection A3.6.5, “Connecting Output Devices.”
*2
:
The module does not contain any fuse but incorporates a short-circuit protector function. Note that the function
protects against short-circuit only when the polarity of the external power supply is correct.
*3:
The contact operation of the output block of the circuit and the LED display operate independently and thus may be
inconsistent in the event of an error.
*4:
For information on the module’s behavior during a CPU failure, see subsection A4.3.3, “Indicating Problem Severity
and Status of Output Module.”
CAUTION
Make sure that the polarity of the external power supply is correct.
If incorrect polarity and shorted load occur at the same time, the output element will be
damaged and smoking or scattering chips may occur.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...