A4-10
IM 34M06C11-01E
A4.5
CPU Module Reset and Memory Clearance
(1) For the F3SP66, F3SP67, F3SP71 and F3SP76
Reset
- Using the FA-M3 Programming Tool WideField3:
Select [Online]–[Extended Functions]–[Reset Start] from the menu bar.
T
For details, refer to the FA-M3 Programming Tool WideField3 (IM 34M06Q16-
E).
The operations can also be carried out using the FA-M3 Programming Tool WideField2 for F3SP66-4S and F3SP67-
6S.
- Using the smart access function:
Execute the Press & Hold operation (with MODE switch value = 0, 1, 2 or 3) of the
rotary switch function, or execute a Reset CPU command of the card batch file
function.
T
For details, refer to the Sequence CPU – Functions (for F3SP66-4S, F3SP67-6S) (IM 34M06P14-01E) or the
Sequence CPU Instruction Manual – Functions (for F3SP71-4N/4S, F3SP76-7N/7S) (IM 34M06P15-01E).
- Using the FTP function (for F3SP66/F3SP67, F3SP71-4S and F3SP76-7S only):
Execute the Reset CPU command of the virtual directory function.
T
For details, refer to the Sequence CPU – Network Functions (for F3SP66-4S, F3SP67-6S) (IM 34M06P14-02E) or the
Sequence CPU Instruction Manual – Functions (for F3SP71-4N/4S, F3SP76-7N/7S) (IM 34M06P15-01E). F3SP71-
4N and F3SP76-7N do not support the virtual directory function.
Memory clearance
Select [Online]–[Extended Functions]–[Clear Devices] from the menu bar of the FA-M3
Programming Tool WideField3.
T
For details, refer to the FA-M3 Programming Tool WideField3 (IM 34M06Q16-
E).
The operations can also be carried out using the FA-M3 Programming Tool WideField2 for F3SP66-4S and F3SP67-6S.
Restoring factory settings
Execute the Press & Hold operation (with MODE switch value = C) of the rotary switch
function.
T
For details, refer to the Sequence CPU – Functions (for F3SP66-4S, F3SP67-6S) (IM 34M06P14-01E) or the Sequence
CPU Instruction Manual – Functions (for F3SP71-4N/4S, F3SP76-7N/7S) (IM 34M06P15-01E).
Note
T
- Restoring the factory settings when the rotary switch function is disabled by
using function removal (for F3SP66/67/71/76)
The Press & Hold operation cannot be used to restore the factory settings when the
rotary switch function is disabled by using function removal.
TIf this situation happens, follow the instructions given below.
T
Set the rotary switch (MODE switch) to C, install a sequence CPU module in the 5th or
higher slot, and turn on the power. After making sure the RDY lamp comes on, turn off
the power. This restores the factory settings.
T
Executing the above-mentioned procedure without setting the rotary switch (MODE
switch) to C clears information other than the project and CPU properties information
stored in the internal ROM.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...