Relative
Index
Parameter Name
Description
Default
Value
Read/
Write
gain calibration, low position
calibration, high position
calibration, transducer
calibration and servo PID
auto tuning.
96
XD_COMMAND_STATE
It shows what is the
calibration is running.
0 r
97
XD_ALERT_ENABLE
This parameter can be used
to enable the available alerts
separately. The alerts are:
0:CYCLE_CNTR - check if
the valve exceeds the cycle
limit.
1:TRAVEL_CNTR - check if
the valve exceeds the total
travel limit
2:TEMP_MAX_MIN - check if
the electronic board
temperature exceeds the
maximum and minimum
value.
3: DEVIATION - check if the
valve position exceed the SP
more than the allow time.
4:POSITION_HI - check if
the valve exceeds the high
position limit.
5:POSITION_LO- checks if
the valve exceeds the low
position limit.
0 r,w
98
XD_ALERT_SUMMARY
Shows the alerts enable that
is ON in the moment.
0:CYCLE_CNTR
- ON
if TOTAL_VALVE_TRAVEL
>= TOT_VALVE_TRAV_LIM
1: TRAVEL_CNTR
- ON
if TRAVEL_COUNT >=
TRAVEL_COUNT_LIMIT
2:TEMP_MAX_MIN
- ON
if INTERNAL_TEMP >=
INTERNAL_TEMP_MAX or
INTERNAL_TEMP <=
INTERNAL_TEMP_MIN
3:DEVIATION
-
ON
if the following sentence are
TRUE for more than
SP_DEVIATION_TIMEOUT:
0 r