Diagnosis: Detailed status information about the field device’s
operating condition. Health of device (not process). The
status are:
Hardware electronic failure – temperature sensor is measuring
temperature out of operation temperature. The operation range is [-
40°C, 85°C];
Hardware mechanic failure – not implemented;
Motor temperature too high – not implemented;
Electronic temperature too high – the electronic temperature is
above 85°C;
Memory check error – At device initialization, it was detected that
some values are out of range and a factory initialization will be
executed automatically;
Measurement failure – not implemented;
Device not initialized – not implemented;
Self-calibration failure – the last auto calibration failed;
Zero point is out of range – not implemented;
Power supply failure – not implemented;
Configuration not valid – not implemented;
Warm startup – the data was recovered successful from non-volatile
data;
Cold startup – the data was set to factory default values;
Maintenance is required – the valve position is been reading out of
the limits plus the position dead band;
Ident number violation – not implemented.
Write Locking: Set the write protection by software.
HW Write Protection: This parameter shows the status of hardware write
protection.
The board has a dipswitch named SW4, where is possible to set the
hardware write protection.
Factory Reset: A selection of reset procedures, which are executed by
pressing the “Execute” button. These procedures are:
-No function: Do nothing;
- Factory Reset: Resets the device and sets most of the device’s
parameters to the default factory values;
- Warm start: Resets the device;
- Reset Address to ‘126’: Resets the device and set the node
address to 126.
FEATURE (Supported): Indicates which optional features are implemented in the
device.
FEATURE (Enabled): Indicate the status of the implemented optional features.
Condensed
Status/Diagnosis:
Enable or disable the Condensed Status/Diagnosis.