Relative
Index
Parameter Name
Description
Default
Value
Read/
Write
|WORKING_SP -
WORKING_POSITION| >=
(SP_DEV
SP_DEVIATION_DB)
4: LOW PRESSURE
- ON
when the LOW PRESSURE
line from motor is ON.
5:POSITION_HI
- ON
when the
WORKING_POSITION >=
POSITION_HI_ALERT
6:POSITION_LO -
ON
when the
WORKING_POSITION <=
POSITION_LO_ALERT.
99 XD_RESET_COUNTERS
This parameter will reset all
counters used for alert or
reset each counter
separately.
0 R,w
100
TOTAL_TRAVEL_DB
In units of TRAVEL_COUNT.
This parameter will setup a
dead band to assume that
the valve is totally open or
totally close to be used by
the
TOTAL_TRAVEL_COUNT.
Change this value will
change the values of
TRAVEL_LIMIT_LOW and
TRAVEL_LIMIT_UP
2.5% r,w
101 TRAVEL_COUNT_UNITS UNITS used to show the
TRAVEL_COUNT
1342: %
r,w
102
TRAVEL_COUNT
Counter the total valve
movement. The unit is
defined in the
TRAVEL_COUNT_UNITS.
0 r,w
103 TRAVEL_COUNT_DEADBAND
The minimum movement to
increase the
TRAVEL_COUNT. The unit
is defined in the
TRAVEL_COUNT_UNITS.
0.6% r,w
104 TRAVEL_COUNT_LIMIT
Travel limit to indicate the
TRAVEL_CNTR alert.
0 r,w
105
INTERNAL_TEMP_MIN
Minimum temperature to start
the indication of
TEMP_MAX_MIN alert.
"-40ºC" r,w
106
INTERNAL_TEMP_MAX
Maximum temperature to
start the indication of
80ºC r,w