10.5.4
Full Stroke Test
The Full Stroke test will get a valve signature. It is possible to store into device a
reference curve and the curve capture in the last full stroke test (FST).
The valve should be full close; otherwise the test will not start and return an error.
Stroke Time Unit: Unit used by all full stroke test parameters.
Break Timeout: Limit time allowed to the valve start to move, otherwise the FST will
fail because the valve exceed the maximum break time.
Timeout: Limit time allowed to the valve complete the full stroke.
Measured Break Time: The break time of the current curve.
Time Interval:
Time interval to complete the test.
Start Test:
Use it to start the FST.
Save Reference Curve: This option will save the last curve as reference. The
measured break time and time interval will be saved as well.