5.8.2 Automatic Calibration (ACAL)
The Automatic Calibration
(ACAL) performs several
self-adjustments, as well
as a zero calibration, a
span calibration, and
tunes the positioner’s PID
gain settings. From the
normal operation screen,
press the CAL button until
ACAL is shown on the
display (the ACAL routine
is shown to the right).
Press and hold the CAL
button until it starts the
automatic calibration
Automatic calibration goes
through five sequences,
when complete it goes back to ACAL Manu. This Calibration is adequate for most
applications. If no advanced calibration is required proceed to Section 5.8.3 to exit
calibration.