Supply Pressure: Pressure of manifold output port A - It is located in the port A. Its
unit is defined in the PRESSURE_UNITS.
The accuracy over the span is ± 2% between 0 - 50ºC.
The offset has a variation of 3.5% for each 1ºC of variation.
If the unit is %, then 100% is the maximum pressure used in the
calibration.
Internal
Temperature:
Electronic board temperature in units as defined in the
INTERNAL_TEMP_UNIT parameter.
10.4.3
Readback & Setpoint (AO)
Located at third tab of Process Variable && Trend curves, this tab displays as bar graph
the values of following Analog output (AO) block parameters: setpoint, readback, valve
position and checkback.
Readback Value: Analog output feedback. This parameter receives the