Available Alerts:
Enable disable device performance diagnostics.
CYCLE_CNTR - check if the valve exceeds the cycle limit.
TRAVEL_CNTR - check if the valve exceeds the total travel limit
TEMP_MAX_MIN - check if the electronic board temperature
exceeds the maximum and minimum value.
DEVIATION - check if the valve position exceed the SP more than
the allow time.
POSITION_HI - check if the valve exceeds the high position limit.
POSITION_LO- checks if the valve exceeds the low position limit.
LOW_PRESSURE-checks if the supply pressure is below the
minimum.
COMM_PROBLEM-check if the modem is detecting bus activity
Alert Summary:
It will report an alert condition if it was enabled at available alerts.
DEVIATION_ALR - ON if the following sentence are TRUE for more
than Setpoint Deviation Timeout: |WORKING_SP -
WORKING_POSITION| >= (SP_DEV
SP_DEVIATION_DB)
CYCLE_CNTR_ALR - ON if Total_Valve_Travel >=
Limit_Total_Valve_Travel