Fault State Option: Action to be taken in case of BAD status of
POSITIONING_VALUE.
Closed Position Deviation: Shows the deviation from the closed position in the
closed position of the last calibration. (in% of span)
Close Time Interval: Last time interval to travel from opened to closed
position in seconds.
Open Time Interval: Last time interval to travel from closed to opened
position in seconds.
Stroke Time Unit: Time unit to be used in the SPSR test.
FST Test Pause: The pause before continuing the last half of the
stroke test (unit defined by STROKE_TIME_UNITS
parameter)
Break Timeout (FST): Time limit to wait for the first valve movement in the
full stroke test.
Timeout (FST): Time limit to wait the finish of full stroke test.
Measured Break Time (FST): Measured break time of the last full stroke test.
Time Interval (FST): Measured of last full stroke test time interval.
Time and Date: Current date from RTC (TIME_AND_DATE
parameter). Write in this parameter to adjust the
RTC.
The DTM will display the time and date format
according to what is defined on Windows (see time
and date format configurations in Windows Control
Panel in order to change it). Setting a new
TIME_AND_DATE value must follow the same
format; otherwise, the DTM will reject it.
Independent to what's defined in Windows settings,
the device will store the values according to its data
type (MM/DD/YY HH:MM:SS), so the year is just a
two digits number.
LCD Contrast: Changes the contrast of the LCD, The range is [26,
63].
This contrast will be use when the electronic
temperature is between -5ºC and 60ºC.
If the electronic temperature is equal or below -5ºC
the contrast will be set automatically to 63.
If the electronic temperature is equal or above 60ºC
the contrast will be set automatically to 26.
WSN Password: Password to enable to change the serial number
WSN Control Flag: This flag will inform if the serial number was
changed properly.
WSN Serial Number: Show the current serial number. To write a new
value, the password in the WSN Password
parameter must be correct.
Revision ID: Firmware revision identification.