WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013
TECH-477/D.W.O. 21424
Page 170 of 206
Normal Mode: The mode which the block uses during normal
operation conditions.
Alarm Summary
Current State Alarm Sum: The alarm sum of the current alarm state.
Unacknowledged State Alarm
Sum:
The alarm sum of the unacknowledged alarm state.
Unreported Stated Alarm Sum: Unreported State Alarm Sum.
Disabled State Alarm Sum: Disabled State Alarm Sum.
Device
Software revision:
Firmware version
Hardware Revision: Electronic board version
Manufacturer: Identification
of device manufacture. Westlock
manufacture ID is 77. The DTM will show the text
“Westlock Controls”.
Device ID: Westlock device identification. The DTM will show the
text “ICoT PA”.
Device Serial Number: Unique serial number
Diagnosis
Diagnosis:
Detailed status information about the field device’s
operating condition. Health of device (not process).
The status are:
Hardware electronic failure – temperature sensor is measuring
temperature out of operation temperature. The operation range is
[-40°C, 85°C];
Hardware mechanic failure – not implemented;
Motor temperature too high – not implemented;
Electronic temperature too high – the electronic temperature is
above 85°C;
Memory check error – At device initialization, it was detected
some values out of range and a factory initialization will be
executed automatically;
Measurement failure – not implemented;
Device not initialized – not implemented;
Self-calibration failure – the last auto calibration failed;
Zero point is out of range – not implemented;
Power supply failure – not implemented;
Configuration not valid – not implemented;
Warm startup – the data was recovered successful from non-
volatile data;
Cold startup – the data was set to factory default values;
Maintenance is required – the valve position is been reading
out of the limits plus the position dead band;
Ident number violation – not implemented.
Diagnosis Mask: Enable or disable the Condensed Status/Diagnosis.