25. Press Close to return to ProfiCaptain.
26. Select the ICoT icon into ProfiCaptain
Network Sheet.
27. The communication will start. We will see a
green circle in the ICoT icon.
28. Click on Watch/Modify I/O to open Watch
I/O dialog.
29.
To change the AO.SP.value via I/O set
Memory Address as 0, Memory Type as
Output, Data Type as Float (IEEE 754)
and click on "Add Watch".
30. To change the AO.SP.status via I/O set
Memory Address as 4, Memory Type as
Output, Data Type as Unsigned8 (byte)
and click on "Add Watch".
31. To see the AO.READBACK.value via I/O
set Memory Address as 0, Memory Type
as Input, Data Type as Float (IEEE 754)
and click on "Add Watch".
32. To see the AO.READBACK.STATUS via
I/O set Memory Address as 4, Memory
Type as Input, Data Type as Unsigned8
(byte) and click on "Add Watch".
33. To see the AO.POS_D.value (discrete
position) via I/O set Memory Address as 5,
Memory Type as Input, Data Type as
Unsigned8 (byte) and click on "Add
Watch".
34. To see the AO.POS_D.status (discrete
position) via I/O set Memory Address as 6,
Memory Type as Input, Data Type as
Unsigned8 (byte) and click on "Add
Watch".
35. To see the AI.OUTPUT.value (position) via
I/O set Memory Address as 7, Memory
Type as Input, Data Type as Float (IEEE
754) and click on "Add Watch".
36. To see the AI.OUTPUT.status (position)
via I/O set Memory Address as 11,
Memory Type as Input, Data Type as
Unsigned8 (byte) and click on "Add
Watch".
37. Also you can add a comment in the Watch
I/O Dialog to make easier to identify the
variable.