The table below will show all the possibility of valve fault state position with the combination
of analog output fault state feature and transducer fault state feature.
AO
SP.STATUS
AO
FSAVE_TYPE
TRD
FAULT_STATE_OPTION
VALVE SP
GOOD -
-
AO.SP.VALUE
UNCERTAIN -
-
AO.SP.VALUE
BAD
2
0
LAST VALID VALUE OF AO.SP
BAD 2
1
0
BAD 2
2
100
BAD 2
3
TRD.
FAULT_STATE_VAL
BAD
1
0
LAST VALID VALUE OF AO.SP
BAD 1
1
0
BAD 1
2
100
BAD 1
3
TRD.
FAULT_STATE_VAL
BAD 0
0
AO.
FSAVE_VALUE
BAD 0
1
AO.
FSAVE_VALUE
BAD 0
2
AO.
FSAVE_VALUE
BAD 0
3
AO.
FSAVE_VALUE
8.3.6 Slot
Any function block parameter and any object can be accessed using slot/index. The ICoT
PA has one block in each slot and each block starts at index 16.
Table 8-2
has the
mapping slot x block.
Each block start in the index 16 of the slot it is located. Then to read a specific parameter it
is necessary to get the slot where the function block is located and add 16 in the parameter
relative index.
For instance, the reference for OUT parameter of Analog Output function block is slot 1,
index 53 = 16 (analog output start index) + 37 (OUT relative index).
Table 8-2
Slot
Index
Description
0 16
Physical
Block
1 16
Analog
Output
2 16
Analog
Input
3 16
Transducer
Block
8.3.7 The Physical Block
The Physical block contains parameters to show and/or manipulate device hardware itself and
firmware specific characteristics associated with the ICoT PA. The Physical block contains no direct