Flow Type: Set the type of set point characterization curve. The following
options are available:
-
Linear
: the analog output setpoint from the analog output is set directly to the
servo PID setpoint;
-
Equal Percentage
: the analog output setpoint is used as a parameter for the
equal percentage function to set the servo PID setpoint;
-
Quick Opening
: the analog output setpoint is used as a parameter for the
quick opening function to set the servo PID setpoint;
-
User defined (table):
the analog output setpoint is characterized using a table
defined by the user to set the servo PID setpoint. (
See the Characterization
Curve section to get details how to enter this table).
Min Number of
Coordinates:
Informs the minimal number of coordinates supported by the
device.
Max Number of
Coordinates:
Informs the maximum number of coordinates supported by the
device.
Number of
Coordinates:
The actual number of coordinates currently stored in the device.
Change this parameter to the intended number of coordinates
before setting up a new curve.
Status
(Characterization):
Current status of the transmitted table. This parameter will display
one of the following status:
-
Not initialized
: There is no valid curve to use;
-
Good
: The written table is valid, and ready to be saved;
-
Table is currently loaded
: The table is ready to be used;
-
Sorting and checking of Table
: Sorting and checking the written table;
-
Not monotonous increasing:
- Not monotonous decreasing:
-
Not enough values transmitted:
The written table has less than the minimum
number of coordinates;
-
Too many values transmitted:
Exceeded the maximum number of
coordinates;
-
Gradient of edge too high:
- Values not accepted:
The written table doesn’t have all the requisites of a
valid curve.
Some status may additionally contain a “(old table is valid)” or
“(table is not initialized)”, these will inform if there is a table saved
for use besides the one that is been currently been edited.
Coordinate: X and Y values of the selected coordinate. The number of
instances of this parameter that the DTM will show is determined
by the value defined in the TAB_ACTUAL_NUMBER parameter.
9.9 PA Profile
9.9.1 Physical Block
9.9.1.1 Standard Parameters