the state from OPEN to CLOSED.
Travel Time OPEN: Set point for the time in seconds between the changes of
the state from OPEN to CLOSED.
Opening Speed Limit: Used to reduce the speed of the open valve movement.
This parameter will change the value of
TRAVEL_RATE_DEC for a value equal to one of the
fallowing options:
-
Slowest
: 20% Dynamic Speed;
-
Slow
: 40% Dynamic Speed;
-
Normal
: 60% Dynamic Speed;
-
Fast
: 80% Dynamic Speed;
-
Fastest
: 100% Dynamic Speed;
-
Custom
: Uses the travel rate defined in the Travel Time CLOSE filed
(TRAVEL_RATE_DEC parameter).
Closing Speed Limit: Used to reduce the speed of the close valve movement.
This parameter will change the value of
TRAVEL_RATE_INC for a value equal to one of the
following options:
-
Slowest
: 20% Dynamic Speed;
-
Slow
: 40% Dynamic Speed;
-
Normal
: 60% Dynamic Speed;
-
Fast
: 80% Dynamic Speed;
-
Fastest
: 100% Dynamic Speed;
-
Custom
: Uses the travel rate defined in the Travel Time CLOSE filed
(TRAVEL_RATE_INC parameter).
Close Time Interval: Last time interval to travel from opened to closed position
in seconds.
Open Time Interval: Last time interval to travel from closed to opened position
in seconds.
10.3.9 Clock
The clock is showed as subdirectory of ICoT PA, Figure 10-4, where is possible to
check the current values, and an option in the device menu, Figure 10-5, where it is
possible to write at available parameters. To allow the user to configure the time and
date of the device’s RTC, goes to Device option at menu bar and select the option
clock, Figure 10-6.
Figure 10-4