to be used by an engineering tools;
The address range 0 up to 125 can be used for any PROFIBUS device.
5.9 Description of Menus
The calibration functions of the positioner are organized into the following four menus:
Menus
•
Menu 1:
ACAL (Automatic Calibration)
•
Menu 2:
MCAL (Manual Calibration)
•
Menu 3:
Cofg (Configuration)
•
Menu 4:
Stro (Manual Override of Input Signal)
•
Menu 5:
Node Add (PA node address assignment)
Menu descriptions are as follows:
Menu 1: ACAL (Automatic Calibration)
Entering this menu allows you to initiate an approximately seven minute self-calibration function.
The positioner will automatically bypass the setpoint and it will enter digital control mode and
perform a calibration
in the following sequence:
Function
1.
-Snsr-
Sensor Calibration
2.
-Lo-
Low (Zero) Calibration
3.
-Hi-
High (Span) Calibration
4.
-Trnd-
Transducer Calibration
5.
-Auto-
Automatic PID Tuning
Menu 2: MCAL (Manual Calibration)
Entering this menu allows you access to the following four calibration functions via the keypad:
1.
-Lo-
Low (Zero) Calibration
2.
-Hi-
High (Span) Calibration
3.
-PID-
Proportional, Integral and Derivative Gain Adjustment
4.
-Snsr-
Sensor Calibration
5.
-Trnd-
Transducer Calibration
Menu 3: Cofg (Configuration)
Entering this menu allows you access to the following five configuration functions via the keypad:
1.
-Flow-
Positioner Output Flow Characteristics
2.
-Type-
Positioner Recognition of Magnetic Feedback, Rotary or Linear
3.
-Flop-
Positioner Fail Position, Open or Closed
4.
-OPSP-
Positioner Opening Speed Adjustment
5.
-CLSP-
Positioner Opening Speed Adjustment
6.
-EDb-
Positioner Operating Dead-band Adjustment
7.
-Cutoff-
Setpoint cutoff adjustment
8.
-Cycle cnt-
Cycle count adjustment