PROFIBUS Ident Number:
Device Ident number in use. The hexadecimal number
0E88 is the specific identification number assigned to
ICoT PA.
Static Revision No.:
Counter used to indication of any change in a static
parameter from function block
Diagnosis :
Detailed status information about the field device’s operating condition.
The status are:
Hardware electronic failure – temperature sensor is measuring temperature out of
operation temperature. The operation range is [-40°C, 85°C];
Hardware mechanic failure – not implemented;
Motor temperature too high – not implemented;
Electronic temperature too high – the electronic temperature is above 85°C;
Memory check error – At device initialization, it was detected that some values are out
of range and a factory initialization will be executed automatically;
Measurement failure – not implemented;
Device not initialized – not implemented;
Self-calibration failure – the last auto calibration failed;
Zero point is out of range – not implemented;
Power supply failure – not implemented;
Configuration not valid – not implemented;
Warm startup – the data was recovered successful from non-volatile data;
Cold startup – the data was set to factory default values;
Maintenance is required – the valve position is been reading out of the limits plus the
position dead band;
Ident number violation – not implemented.
Diagnosis mask: Enable/disable any diagnosis bit
Feature supported:
Profibus feature supported
Feature enable: Features are current enable
Condensed Status/Diagnosis:
Enable/Disable the condensed status
10.5.3 Alert
The Alert option under the Diagnostics menu has device performance diagnostics and
alerts.