background image

 

 

Smart Positioner   YT-2700L,R  Installation manual 

 

Installation

  

 

Safety Warning  

When installing a positioner, please ensure to read and follow safety instruction.   

  All input and supply pressure to valve, actuator, and other related devices must be turned 

off.   

  Use bypass valve or other equipment to avoid entire system "shut down."   

  Make sure there is no remaining pressure in the actuator.  

 

Tools for Installation  

 Hexagonal wrench 

 

 Screw drivers (+) & (

-)  

 Spanners for hexagonal

-head bolts  

 

YT-2700L Installation  

YT-2700L should be installed on linear motion valve such as globe valve or gate valve using spring 

return type of diaphragm or piston actuator.  Before installation, be sure to check for following 

installation components.  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1)  Proper bracket must be made in order to attach positioner on the actuator yoke.  Please 

consider following when making a bracket.  

  Feedback lever should be leveled at 50% of the valve stroke.  (Refer to Step 7) 

  Feedback lever connection bar of actuator clamp should be installed at the positioner 

that the valve stroke and numbers which indicated on the feedback lever must be fitted.  
(Refer to Step 8) 

 

2)  Attach YT-2700L to the bracket, which was made in earlier 

step, by using bolts.  <Figure 2>  Please refer to backside of 
the product for size of the bolts.  The standard size of bolt is 
M8 x 1.25P, and other bolt sizes are available.  Please 
contact YTC sales department.   

 
 

Young Tech Co.  #662-8 PumgMu Dong, Kimpo City, (415-809) Korea  (031) 986-4935   www.ytc.co.kr

 

Reviews:

Related manuals for YT-2700L