Chapter 3 Profibus DP
Manual VIPA System 200V
3-14
HB97E - IM - Rev. 06/29
The module carries a number of LEDs that are available for diagnostic
purposes on the bus and for displaying the local status. The following table
explains the different colors of the diagnostic LEDs.
Label
Color Description
R
green If R is the only LED that is on, then the master status is
RUN. The slaves are being accessed and the outputs
are 0 ("Clear" state).
If both R+DE are on the status of the Master is
"operate". It is communicating with the slaves.
Blinks 3 times: Transfer from MMC to Flash-ROM
without error.
E
red
On at slave failure (ERROR).
Blinks 3 times: Transfer from MMC to Flash-ROM
without error.
IF
red
Initialization error for bad parameterization
DE
green DE (Data exchange) indicates Profibus communication
activity. At the DP master with the order no. 208-1DP01
this LED is yellow.
MC
yellow Blinks at reading the parameters from MMC. Is on at
wrong parameterization.
The VIPA Profibus master is connected to your Profibus network via the
9pin socket. The following figure shows the assignment of the individual
pins:
Pin
Assignment
1 shield
2 n.c.
3
RxD/TxD-P (Line B)
4 RTS
5 M5V
6 P5V
7 n.c.
8
RxD/TxD-N (Line A)
9 n.c.
The IM 208DPO is connected to Profibus by a FOL (
f
iber
o
ptic
l
ink)
interface. The layout of this interface is shown below:
Connect to receive line (from slave)
Connect to send line (to slave)
Components
LEDs
RS485 interface
(at IM 208DP)
FOL interface
(at IM 208DPO)
5
4
3
2
1
9
8
7
6
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...