Chapter 4 Interbus
Manual VIPA System 200V
4-18
HB97E - IM - Rev. 06/29
Technical data
Electrical data
VIPA 253-1IB00
Power supply
DC 24V (20.4 ... 28.8) via front from ext. power supply
Current consumption
max. 300mA
Output current backplane bus
max. 3.5A
Isolation
≥
AC 500V , according to DIN 19258
Status indicators
via LEDs located on the front
Connections / interfaces
9pin D-type (plug)
inbound
remote bus
9pin D-type (socket)
outbound
remote
bus
Interbus interface
Connection
remote bus, 9pin D-type as per DIN 19258
Network topology
Ring with an integrated return line
Medium
Screened twisted pair cable
Data transfer rate
500kBit/s
Total length
12.8km
Distance between two stations
400m
digital inputs/outputs
max.160 input bits and 160 output bits
max. no. of stations
256
Combination with peripheral modules
max. no. of modules
16
max. digital I/O
16 (process data width 20 I / 20 O)
max. analog I/O
4 (process data width 10 I / 10 O)
no configuration possible
Dimensions and weight
Dimensions (WxHxD) in mm
25.4x76x78
Weight 80g
Interbus coupler
IM 253IBS
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...