Alarm status at diagnostic alarm Bytes x+4 to x+7
(corresponds CPU diagnostic record set 0)
Byte
Bit 7 ... Bit 0
x+4
Bit 0: Module malfunction, i.e. a problem has been detected
Bit 1: Internal error in the module
Bit 2: External error - module no longer addressable
Bit 3: Channel error in the module
Bit 4: Load power supply is missing
Bit 5: Front connector is missing
Bit 6: Module is not parameterized
Bit 7: Parameter assignment error
x+5
Bit 0 ... 3: Module class
1111:
Digital
module
0101:
Analog
module
1000:
FM
1100:
CP
Bit 4: Channel information available
Bit 5: User information available
Bit 6: always "0"
Bit 7: always "0"
x+6
Bit 0: Memory or coding key analog module is missing
Bit 1: Communication error
Bit 2: Operating mode
0:
RUN
1:
STOP
Bit 3: Cycle time monitoring addressed
Bit 4: Module power supply failure
Bit 5: Empty battery
Bit 6: Complete backup failure
Bit 7: always "0"
x+7
Bit 0: reserved
Bit 1: reserved
Bit 2: reserved
Bit 3: reserved
Bit 4: reserved
Bit 5: reserved
Bit 6: Process interrupt lost
Bit 7: reserved
Continued …
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...