Manual VIPA System 200V
Chapter 3 Profibus DP
HB97E - IM - Rev. 06/29
3-99
Electrical data
VIPA 208-1DP11
Power supply
via backplane bus
Current consumption
max. 450mA
Isolation
≥
AC 500V
Status indicator
via LEDs on the front
Connections/interfaces
2pin socket for fiber optic cable Profibus interface
Profibus interface
Connection
2pin socket for fiber optic cable
Network topology
Linear structure with dual FO cable, no bus terminator
required
Medium
dual-core fiber optic cable
Data transfer rate
12MBaud
Total length
at POF-FO: max. 50m between stations
at HCS-FO: max. 300m between stations
Max. no. of stations
17 stations incl. Master
Combination with peripheral modules
max. no of slaves
16
max. no. of input bytes
256 (1024 since v3.0.0)
max. no. of output bytes
256 (1024 since v3.0.0)
Dimensions and weight
Dimensions (WxHxD) in mm
25.4x76x78
Weight 110g
The maximum number of DPO participants depends on the baud rate. The
table shows the max. number incl. master:
Baud rate
max. no. of participants
≤
1.5MBaud
17
3MBaud 15
6MBaud 7
12MBaud 4
IM 208DPO
Max. number of
stations
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...