![VIPA System 200V IM Series Manual Download Page 301](http://html1.mh-extra.com/html/vipa/system-200v-im-series/system-200v-im-series_manual_1029241301.webp)
Manual VIPA System 200V
Chapter 7 SERCOS - Spare part
HB97E - IM - Rev. 06/29
7-19
For example, the following values shall be set:
AI 4x16Bit (231-1BD52) at position 1
Length: 10Byte
Parameter:
Byte
Description
Set property
Handling value
0
Diagnostic alarm Byte:
deactivated
00h = 0dez
1
reserved
00h
00h = 0dez
2
Function no. channel 0
Voltage
±
10V in the S7
format from Siemens
28h = 40dez
3
Function no. channel 1
Voltage
±
10V in the S7
format from Siemens
28h = 40dez
4
Function no. channel 2
Current 4...20mA in S7
format from Siemens
2Dh = 45dez
5
Function no. channel 3
Current 4...20mA in S7
format from Siemens
2Dh =45dez
6
Option Byte channel 0
default
00h = 0dez
7
Option Byte channel 1
default
00h = 0dez
8
Option Byte channel 2
default
00h = 0dez
9
Option Byte channel 3
default
00h = 0dez
Herefore the table has the following entries:
P-0-0100
1.SLOT
At position 1 is a parameterizable
module
P-0-0101 1.LENGTH
10dez
P-0-0102 1.PARAMETER.0
0dez
P-0-0103 1.PARAMETER.1
0dez
P-0-0104 1.PARAMETER.2
40dez
P-0-0105 1.PARAMETER.3
40dez
P-0-0106 1.PARAMETER.4
45dez
P-0-0107 1.PARAMETER.5
45dez
P-0-0108 1.PARAMETER.6
0dez
P-0-0109 1.PARAMETER.7
0dez
P-0-0110 1.PARAMETER.8
0dez
P-0-0111 1.PARAMETER.9
0dez
P-0-0112 1.PARAMETER.10
...
...
are created but not used
P-0-0117 1.PARAMETER.15
Set the value in
P-0-0000
to 1 and the parameters are stored in the
EEPROM of the SERCOS coupler.
At successful transfer, you get the return value 0 and at the analog input
module the LEDs F2 and F3 for wirebreak recognition are illuminated due
to the current measuring range.
Example
parameterization
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...