Chapter 6 DeviceNet
Manual VIPA System 200V
6-22
HB97E - IM - Rev. 06/29
Technical data
Electrical data
VIPA 253-1DN00
Power supply
DC 24V (20.4 ... 28.8) via front from ext. power supply
Current consumption
Bus coupler: 50mA
incl. supply to the peripheral modules: 800mA max.
Output current backplane bus
3.5A
Isolation
between DeviceNet and backplane bus
500V rms
Function specific data
Status indicator
by means of LEDs on the front
Physical connection to DeviceNet
5pin Open Style connector
Network topology
Linear bus, tap lines up to 6m length
Communication medium
Screened 5core cable
Communication rate
125, 250, 500kBaud
Overall length of the bus
up to 500m
Number of stations
max. 64
Combination with peripheral modules
Number of modules
max. 32
Inputs max.
256Byte
Outputs max.
256Byte
Dimensions and Weight
Dimensions (BxHxT)
25.4x76x78mm
Weight 80g
DeviceNet coupler
IM 253DN