Manual VIPA System 200V
Chapter 3 Profibus DP
HB97E - IM - Rev. 06/29
3-23
12. Transfer the wld-file to the MMC by means of a MMC reading
device.
13. Plug-in the MMC memory module into your IM 208DP master
14. Turn on the power supply for the System 200V.
15. Hold the operating mode lever of the Profibus master in position MR
until the blinking MC-LED switches to permanent on.
16. Release the operating mode lever and tip it once more to MR.
→
The data is transferred from the MMC into the internal Flash-ROM.
During data transfer all LEDs extinguish.
At successful data transfer, the green R-LED blinks 3 times.
At error, the red E-LED blinks 3 times.
RN
ST
MR
RN
ST
MR
RN
ST
MR
Transfer
Tip
R
E
IF
DE
MC
R
E
IF
DE
MC
R
E
IF
DE
MC
R
E
IF
DE
MC
R
E
IF
DE
MC
RN
ST
MR
3Sec.
R
E
IF
DE
MC
RN
ST
MR
RN
ST
MR
OK
Error
3x
3x
17. Now you may release the MMC again.
18. Switch the master from STOP to RUN.
→
The IM 208DP master
now starts with the new project in the internal Flash-ROM.
The RUN-LED (R) and DE are on.
Note!
The project inside the PLC for the 1
st
Master takes priority over the project
downloaded to Flash-ROM of the Master.
If the MMC contains a wld- and a 2bf-file, the wld-file has the priority.
to 2. continued
Transfer data from
MMC to internal
Flash-ROM
IM 208 DP
D
P
R
E
IF
DE
MC
MMC
RN
ST
MR
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...