Technical data
Electrical data
VIPA 208-1CA00
Power supply
via backplane bus
Current consumption
max. 300mA
Isolation
≥
AC 500V
Status indicator
by means of LEDs located on the front
Connectors/interfaces
9pin D-type (socket) CAN-Bus connection
CAN-Bus interface
Connection
9pin D-type plug
Network topology
Linear bus, active bus termination at one end, tap lines
permitted.
Medium
Screened three-core cable, unscreened cable permitted -
depending on environment.
Data transfer rate
10kBaud to 1MBaud
Max. overall length
1000m at 50kBaud without repeaters
Max. no. of stations
127 stations (depending on the master interface)
Combination with peripheral
modules
Max. number of slaves
125
Max. number of TxPDOs
40
Max. number of RxPDOs
40
Max. number of input bytes
384
Max. number of output bytes
384
Dimensions and weight
Dimensions (WxHxD) in mm
25.4x76x78
Weight 110g
CANopen master
IM 208 CAN
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...