![VIPA System 200V IM Series Manual Download Page 106](http://html1.mh-extra.com/html/vipa/system-200v-im-series/system-200v-im-series_manual_1029241106.webp)
Chapter 3 Profibus DP
Manual VIPA System 200V
3-74
HB97E - IM - Rev. 06/29
… Continue
Alarm status at diagnostic alarm Bytes x+8 to x+19
(corresponds CPU diagnostic record set 1)
Byte
Bit 7 ... Bit 0
x+8
70h: Module with digital inputs
71h: Module with analog inputs
72h: Module with digital outputs
73h: Module with analog outputs
74h: Module with analog in-/-outputs
76h: Counter
x+9
Lenght of the channel-specific diagnostic
x+10
Number of channels per module
x+12
Diagnostic event on the channel/channel group 0
Assignment see module description
x+13
Diagnostic event on the channel/channel group 1
Assignment see module description
.
.
.
.
.
.
x+19
Diagnostic event on the channel/channel group 7
Assignment see module description
Alarm status at process alarm Bytes x+4 to x+7
More detailed information to the diagnostic data is to find in the concerning
module descriptions.
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...