Chapter 5 CANopen
Manual VIPA System 200V
5-66
HB97E - IM - Rev. 06/29
Index
Sub-
index
Name
Type
Attr. Map. Default value Meaning
0x1009 0
Manufacturer
Hardware
version
Visible string ro
N
Hardware version number
of bus coupler
VIPA IM 253 1CA01 = 1.00
VIPA IM 253 1CA30 = 1.00
Since the returned value is longer than 4Byte, the segmented SDO
protocol is used for transmission.
Index
Sub-
index
Name
Type
Attr. Map. Default value Meaning
0x100A 0
Manufacturer
Software version
Visible string ro
N
Software version number
CANopen software
VIPA IM 253 1CA01 = 3.xx
VIPA IM 253 1CA30 = 3.xx
Since the returned value is longer than 4Byte, the segmented SDO
protocol is used for transmission.
Index
Sub-
index
Name
Type
Attr. Map.
Default value
Meaning
0x100B 0
Node ID
Unsigned32 ro
N
0x00000000
Node number
The node number is supported for reasons of compatibility.
Index
Sub-
index
Name
Type
Attr. Map. Default value Meaning
0x100C 0
Guard
time
[ms]
Unsigned16 rw
N
0x0000
Interval between two guard
telegrams. Is set by the NMT
master or configuration tool.
Hardware version
Software version
Node number
Guard time
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...