Manual VIPA System 200V
Chapter 5 CANopen
HB97E - IM - Rev. 06/29
5-29
Index
Sub-
index
Name
Type
Attr.
Map. Default value Meaning
0x1017 0
Producer
heartbeat
time
Unsigned16 rw
N
0x0000
Defines the cycle time of
heartbeat in ms
Index
Sub-
index
Name
Type
Attr.
Map. Default value Meaning
0x1018 0
Identity
Object
Unsigned8 ro N 0x04
Contains
general
Information about the device
(number of entries)
1
Vendor ID
Unsigned32 ro
N
0xAFFEAFFE Vendor ID
2
Product
Code
Unsigned32 ro
N
0x2081CA00 Product
Code
3
Revision
Number
Unsigned32 ro
N
Revision
Number
4
Serial
Number
Unsigned32 ro
N
Serial
Number
Index
Sub-
index
Name
Type
Attr.
Map. Default value Meaning
0x1400
...
0x1427
0 Number
of
Elements
Unsigned8 ro N 0x02
Communication
parameter
for the first receive PDOs,
Subindex 0: number of
following parameters
1
COB-ID
Unsigned32
rw
N
0xC0000200
+ NODE_ID
COB-ID RxPDO1
2
Transmis-
sion type
Unsigned8
rw
N
0xFF
Transmission type of the
PDO
Sub-index 1 (COB-ID): The lower 11Bit of the 32Bit value (Bits 0-10)
contain the CAN identifier, the MSBit (Bit 31) shows if the PDO is active (1)
or not(0), Bit 30 shows if a RTR access to this PDO is permitted (0) or not
(1).
The sub-index 2 contains the transmission type.
Producer
Heartbeat Time
Identity Object
Communication
parameter RxPDO
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...