Chapter 3 Profibus DP
Manual VIPA System 200V
3-96
HB97E - IM - Rev. 06/29
To be compatible with the Siemens SIMATIC Manager, you have to
execute the following steps for the CPU 214DP:
•
Start the Hardware configurator from Siemens
•
Install the GSD-file vipa_21x.gsd
•
Project a CPU 315-2DP with DP master (master address 2)
•
Add a Profibus slave
"VIPA_CPU21x"
with address 1.
•
Include the CPU
214-2BP02
at slot 0
•
Select the following parameters for the CPU 214DP:
- Input Add.: 30
- Input Length: 2
- Output Add.: 40
- Output Length: 2
- Prm. Add.: 800
- Diag. Add.: 900
- Stat. Add.: 1020
- Profibus DP Add.: 3
•
Include the output module 222-1BF00 at slot 1 and give them the output
address 0.
•
Safe your project.
Engineering
CPU 214DP