Chapter 3 Profibus DP
HB97E - IM - Rev. 06/29
3-45
IM 253-xDPx0 - DP-V0 Slave - Project engineering
The module is configured by means of your Profibus master configuration
tool. During the configuration you will assign the Profibus slave modules to
your master module.
The direct allocation is defined by means of the Profibus address that you
have to set at the slave module.
The Slaves are projected via gsd-file at the hardware configuration.
Each Profibus module is delivered with a floppy disk by VIPA. The floppy
disc contains all GSD- and type files of the Profibus modules from VIPA as
Cx000023_Vxxx.ZIP file. The assignment of the GSD-file to your slave is
shown in the "Readme.txt" file of Cx000023_Vxxx.ZIP.
Please install the required files from your floppy disc into your configuration
tool. Details on the installation of the GSD and/or type files are available
from the manual supplied with your configuration tool.
The VIPA WinNCS configuration tool already contains all GSD-files for the
VIPA components!
You may also download the GSD-file via the ftp-server
ftp: //ftp.vipa.de/support/profibus_gsd_files
.
After the installation of the GSD-file you will find this entry e.g. in the
hardware catalog from Siemens at:
Profibus DP>Additional field devices>I/O>VIPA_System_200V>
VIPA 253-1DP00
At deployment of Profibus DP slave modules like the VIPA 253-2DP20,
choose "253-2DP20" as module type.
The slot 1 is mandatory, because the module is, seen from the hardware
side, directly beside the slave.
The project engineering of the IM 253DP slave at the DP master from VIPA
is to be find in the description to the DP master in this chapter.
The slave section that achieves firstly the DataExchange state (due to the
system, this is always the most left one), is automatically the active slave
and has the parameterization access at the peripheral modules.
For assigning new parameters to your remote I/O you should notice that
you need an active master-slave-system. Before the transfer of new
parameters is possible, both slaves must be in WAITPARAM state.
General
GSD file
Deployment
IM 253DP,
DO 24xDC 24V
Deployment at a
IM 208DP master
from VIPA
Parameterization
in a redundant
system
Summary of Contents for System 200V IM Series
Page 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Page 2: ...Lerrzeichen...
Page 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Page 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Page 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Page 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Page 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Page 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...